HT Current Transformer & HT Potential Transformer

Resin Cast HT Current Transformer

11 Kv Resin Cast Metering Current Transformer used in Metering Cubicle Panel for  metering Purpose.  The primary current of the CT is transformed into the required secondary current of 5 A or 1 A. Measuring CT’s have different class of accuracy I.e. 0.1, 0.2S, 0.2, 0.5S.

 

  • Ratio: 2. 5/1 A to 500/1A,2.5/5A to 1000/5A
  • Burden: 2. 75 to 20 VA
  • System voltage: 12 kv
  • Class of acc: 0. 5,0.2. 0.2S
  • STC: 150 x IPR
  • Frequency: 50 hz
  • Bil: 12/38/95 kv
  • IS 16227-1& 2

Resin Cast 11KV HT Potential Transformer

11 KV Resin Cast Metering Potential Transformer used in Metering Cubicle Panel for  metering Purpose.  The primary Volatge of the PT  is transformed into the required secondary Voltage 63 V or 110 V. Measuring PT’s have different class of accuracy I.e. 0.5,0.2.

 

  • Ratio: 11kv/√3/110/√3
  • Burden: 15 , 25 , 50 VA
  • System voltage: 12 kv
  • Class of acc: 0. 5 ,0.2
  • Frequency: 50 hz
  • Bil: 12/38/95 kv
  • IS 16227-3

11KV HT Metering & Protection Transformer

11 KV Resin Cast Metering &  Protection Transformer used in Metering VCB Panel for  metering & protection. 

  • Ratio: 30/5P10 to 1000/5P10
  • Burden: 7. 5 VA/15VA
  • Class : 0.5 & 1 & 5P10
  • Frequency: 50 hz
  • Insulation level: 12/28/75 kv
  • Stc: 18 KA for 1sec
  • Ref: IS 16227-1 & 2

11 KVHT 3 Phase Potential Transformer

11 KV  3Phase Voltage Transformer used in Metering VCB Panels. 

  • Ratio: 11000/110V
  • Burden: 100 VA
  • System voltage: 12 kv
  • Class of acc: 0.5 & 1
  • Frequency: 50 hz
  • Bil: 12/38/95 kv